ABB RELION 620 Series Technical Manual page 697

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

1MAC504801-IB E
8.3.7
8.3.8
Table 520:
PQSS Group settings
Parameter
Values (Range)
Reference voltage
10.0...200.0
Voltage dip set 1
10.0...100.0
VVa dip time 1
0.5...54.0
Voltage dip set 2
10.0...100.0
VVa dip time 2
10.0...180.0
Voltage dip set 3
10.0...100.0
VVa dip time 3
2000...60000
Voltage swell set 1
100.0...140.0
Table continues on next page
620 series ANSI
Technical Manual
Voltage variation measurement can be done to the phase-to-earth and phase-to-phase
voltages. The power quality standards do not specify whether the measurement should be
done to phase or phase-to-phase voltages. However, in some cases it is preferable to use
phase-to-earth voltages for measurement. The measurement mode is always TRMS.
Signals
Table 518:
PQSS Input signals
Name
Type
I_A
SIGNAL
I_B
SIGNAL
I_C
SIGNAL
V_A
SIGNAL
V_B
SIGNAL
V_C
SIGNAL
BLOCK
BOOLEAN
Table 519:
PQSS Output signals
Name
Type
TRIP
BOOLEAN
PICKUP
BOOLEAN
SWELLST
BOOLEAN
DIPST
BOOLEAN
INTST
BOOLEAN
Settings
Unit
Step
%Un
0.1
%
0.1
cycles
0.1
%
0.1
cycles
0.1
%
0.1
ms
10
%
0.1
Power quality measurement functions
Default
Description
0
Phase A current
0
Phase B current
0
Phase C current
0
Phase A voltage
0
Phase B voltage
0
Phase C voltage
0=False
Block signal for activating the blocking mode
Description
Voltage variation detected
Voltage variation present
Voltage swell active
Voltage dip active
Voltage interruption active
Default
Description
57.7
Reference supply voltage in %
80.0
Dip limit 1 in % of reference voltage
3.0
Voltage variation dip duration 1
80.0
Dip limit 2 in % of reference voltage
30.0
Voltage variation dip duration 2
80.0
Dip limit 3 in % of reference voltage
3000
Voltage variation dip duration 3
120.0
Swell limit 1 in % of reference voltage
Section 8
691