Section 9
Control functions
756
FR_DIFF_MEAS and PH_DIFF_MEAS. Also, the indications of the conditions that are
not fulfilled and thus preventing the breaker closing permission are available as monitored
data values V_DIFF_SYNC, PH_DIF_SYNC and FR_DIFF_SYNC. These monitored
data values are updated only when the Synchro check enabled with the Synchro check
mode setting and the measured ENERG_STATE is "Both Live".
Continuous mode
The continuous mode is activated by setting the parameter Control mode to "Continuous".
In the continuous control mode, Synchro check is continuously checking the
synchronism. When synchronism is detected (according to the settings), the SYNC_OK
output is set to TRUE (logic '1') and it stays TRUE as long as the conditions are fulfilled.
The command input is ignored in the continuous control mode. The mode is used for
situations where Synchro check only gives the permission to the control block that
executes the CB closing.
Closing
permission
25
GUID-3921CB7B-0BBD-4BB3-B0E7-BFF043900C97 V1 EN
Figure 384:
A simplified block diagram of the Synchro check function in the
continuous mode operation
Command mode
If Control mode is set to "Command", the purpose of the Synchro check functionality in
the command mode is to find the instant when the voltages on both sides of the circuit
breaker are in synchronism. The conditions for synchronism are met when the voltages on
both sides of the circuit breaker have the same frequency and are in phase with a
magnitude that makes the concerned busbars or lines such that they can be regarded as
live.
In the command mode operation, an external command signal CL_COMMAND, besides the
normal closing conditions, is needed for delivering the closing signal. In the command
control mode operation, the Synchro check function itself closes the breaker via the
SYNC_OK output when the conditions are fulfilled. In this case, the control function block
delivers the command signal to close the Synchro check function for the releasing of a
closing-signal pulse to the circuit breaker. If the closing conditions are fulfilled during a
permitted check time set with Maximum Syn time, the Synchro check function delivers a
closing signal to the circuit breaker after the command signal is delivered for closing.
Closing
command
52
1MAC504801-IB E