state. All default settings and configuration files stored in the factory are restored. For
further information on restoring factory settings, see the operation manual.

Load profile record LoadProf

Functionality

The protection relay is provided with a load profile recorder. The load profile feature
stores the historical load data captured at a periodical time interval (demand interval). Up
to 12 load quantities can be selected for recording and storing in a nonvolatile memory.
The value range for the recorded load quantities is about eight times the nominal value,
and values larger than that saturate. The recording time depends on a settable demand
interval parameter and the amount of quantities selected. The record output is in the
COMTRADE format.

Quantities

Selectable quantities are product-dependent.
Table 83:
Quantity Description
Disabled
Quantity not selected
IA
Phase A current, instance 1
IB
Phase B current, instance 1
IC
Phase C current, instance 1
IG
Neutral/ground/residual current, instance 1
IA2
Phase A current, instance 2
IB2
Phase B current, instance 2
IC2
Phase C current, instance 2
IG2
Neutral/ground/residual current, instance 2
IA3
Phase A current, instance 3
IB3
Phase B current, instance 3
IC3
Phase C current, instance 3
VAB
Phase-to-phase AB voltage, instance 1
VBC
Phase-to-phase BC voltage, instance 1
VCA
Phase-to-phase CA voltage, instance 1
VA
Phase-to-ground A voltage, instance 1
VB
Phase-to-ground B voltage, instance 1
VC
Phase-to-ground C voltage, instance 1
Table continues on next page