Section 4
Protection functions
4.1.10.7
Table 194:
46R Group settings
Parameter
Values (Range)
Pickup value
0.05...1.00
Trip delay time
100...60000
Table 195:
46R Non group settings
Parameter
Values (Range)
Operation
1=enable
5=disable
4.1.10.8
4.1.10.9
254

Settings

Unit
Step
xIn
0.01
ms
10
Unit
Step

Monitored data

Table 196:
46R Monitored data
Name
Type
PICKUP_DUR
FLOAT32
46R
Enum

Technical data

Table 197:
46R Technical data
Characteristic
Operation accuracy
1)2)
Pickup time
I
Fault
value
Reset time
Reset ratio
Retardation time
Trip time accuracy in definite time mode
Suppression of harmonics
1) Negative-sequence current before = 0.0, f
measurements
2) Includes the delay of the signal output contact
Default
Description
0.75
Pickup value
100
Trip delay time
Default
Description
5=disable
Operation Disable / Enable
Values (Range)
Unit
0.00...100.00
%
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Value
Depending on the frequency of the measured
current: f
±1.5% of the set value or ±0.002 × I
Minimum
Pickup
= 2.0 × set
22 ms
<40 ms
Typically 0.96
<35 ms
±1.0% of the set value or ±20 ms
DFT: -50 dB at f = n × f
= 60 Hz, results based on statistical distribution of 1000
n
1MAC504801-IB E
Description
Ratio of pickup time / trip time
Status
±2 Hz
n
n
Typical
Maximum
25 ms
28 ms
, where n = 2, 3, 4, 5,...
n
620 series ANSI
Technical Manual