Signals; Settings - ABB RELION 620 Series Technical Manual

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

1MAC504801-IB E
4.6.3.6
4.6.3.7
Table 352:
87LOZREF Group settings
Parameter
Values (Range)
Trip value
5...50
Minimum trip time
40...300000
Restraint mode
1=None
2=Harmonic2
Pickup value 2.H
10...50
Table 353:
87LOZREF Non group settings
Parameter
Values (Range)
Operation
1=enable
5=disable
Reset delay time
0...60000
CT connection type
1=Type 1
2=Type 2
620 series ANSI
Technical Manual
Blocking the starting of the restricted ground-fault protection at the magnetizing inrush is
based on the ratio of the second harmonic and the fundamental frequency amplitudes of
the neutral current IG_2H / IG. Typically, the second harmonic content of the neutral
current at the magnetizing inrush is higher than that of the phase currents.

Signals

Table 350:
87LOZREF Input signals
Name
Type
I_A
SIGNAL
I_B
SIGNAL
I_C
SIGNAL
I
SIGNAL
0
BLOCK
BOOLEAN
Table 351:
87LOZREF Output signals
Name
Type
TRIP
BOOLEAN
PICKUP
BOOLEAN
BLK2H
BOOLEAN

Settings

Unit
Step
%In
1
ms
1
%In
1
Unit
Step
ms
1
Default
Description
0
Phase A current
0
Phase B current
0
Phase C current
0
Zero-sequence current
0=False
Block signal for activating the blocking mode
Description
Trip
Pickup
2nd harmonic block
Default
Description
5
Trip value
40
Minimum trip time
1=None
Restraint mode
50
The ratio of the 2. harmonic to fundamental
component required for blocking
Default
Description
1=enable
Operation Disable / Enable
20
Reset delay time
2=Type 2
CT connection type
Section 4
Protection functions
465