The autoreclosing shot is initiated with a trip signal of the protection function. The
autoreclosing picks up when the protection trip delay time elapses.
Normally, all trip and pickup signals are used to initiate an autoreclosing shot and trip the
circuit breaker. If any of the input signals INIT_X or DEL_INIT_X are used for
blocking, the corresponding bit in the Tripping line setting must be FALSE. This is to
ensure that the circuit breaker does not trip from that signal, that is, the signal does not
activate the OPEN_CB output. The default value for the setting is "63", which means that
all initiation signals activate the OPEN_CB output. The lowest bit in the Tripping line
setting corresponds to the INIT_1 input, the highest bit to the INIT_6 line.
Shot initiation
A070869 V1 EN
Figure 365:
Example of an autoreclosing program with a reclose scheme matrix
In the AR function, each shot can be programmed to locate anywhere in the reclose
scheme matrix. The shots are like building blocks used to design the reclose program. The
building blocks are called CBBs. All blocks are alike and have settings which give the