1MAC504801-IB E
4.6.2.9
Table 346:
87T3 Group settings
Parameter
Values (Range)
High trip value
500...3000
Enable high set
0=False
1=True
Low trip value
5...50
Slope section 2
10...50
End section 2
100...500
Restraint mode
-1=2.h + 5.h + wav
5=Waveform
6=2.h + waveform
7=5.h + waveform
Pickup value 2.H
7...20
Pickup value 5.H
10...50
Stop value 5.H
10...50
Harmonic deblock 2.
0=False
1=True
Harmonic deblock 5.
0=False
1=True
620 series ANSI
Technical Manual
Name
Type
I_C3
SIGNAL
BLOCK
BOOLEAN
BLK_OPR_LS
BOOLEAN
BLK_OPR_HS
BOOLEAN
Table 345:
87T3 Output signals
Name
Type
TRIP
BOOLEAN
OPR_LS
BOOLEAN
OPR_HS
BOOLEAN
BLKD2H
BOOLEAN
BLKD5H
BOOLEAN
BLKDWAV
BOOLEAN

Settings

Unit
Step
%Ir
10
%Ir
1
%
1
%Ir
1
%
1
%
1
%
1
Default
Description
0
Current ID for getting current values for phase 3, tertiary
side or LV restraint
0=False
Block
0=False
Blocks trip outputs from biased stage
0=False
Blocks trip outputs from instantaneous stage
Description
Trip combined
Trip from low set
Trip from high set
2nd harmonic restraint block status
5th harmonic restraint block status
Waveform blocking status
Default
Description
1000
Instantaneous stage setting
1=True
Enable high set stage
20
Basic setting for biased operation
30
Slope of the second line of the operating
characteristics
150
Turn-point between the second and the third
line of the operating characteristics
-1=2.h + 5.h + wav
Restraint mode
15
2. harmonic blocking ratio
35
5. harmonic blocking ratio
35
5. harmonic blocking ratio
1=True
2. harmonic deblocking in case of switch on to
fault
0=False
5. harmonic deblocking in case of severe
overvoltage
Section 4
Protection functions
451