Technical Data; Power Protection; Three-Phase Directional Power Protection 32P; Identification - ABB RELION 620 Series Technical Manual

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

1MAC504801-IB E
4.3.2.9
4.4
4.4.1
4.4.1.1
4.4.1.2
4.4.1.3
620 series ANSI
Technical Manual

Technical data

Table 279:
81LSH Technical data
Characteristic
Operation accuracy
f<
df/dt
Pickup time
f<
df/dt
Reset time
Trip time accuracy

Power protection

Three-phase directional power protection 32P

Identification

Function description
Three-phase directional power
protection

Function block

GUID-78CD7B86-D6C9-4ED8-91C7-E6A0640039CE-ANSI V1 EN
Figure 151:
Function block

Functionality

The three-phase directional power protection 32P is used to detect positive-sequence
power direction. The output of the function is used for blocking or releasing other
functions in protection scheme.
The directional positive-sequence power protection contains a blocking functionality
which blocks function output and resets Timer.
Value
±10 mHz
±100 mHz/s (in range |df/dt| < 5 Hz/s)
± 2.0% of the set value (in range 5 Hz/s < |df/dt| < 15
Hz/s)
<80 ms
<120 ms
<150 ms
±1.0% of the set value or ±30 ms
IEC 61850
IEC 60617
identification
identification
DPSRDIR
I1->
Section 4
Protection functions
ANSI/IEEE C37.2
device number
32P