Settings - ABB RELION 620 Series Technical Manual

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

Section 4
Protection functions
4.1.5.11
Table 167:
67/51N Group settings
Parameter
Values (Range)
Pickup value
0.010...5.000
Pickup value mult
0.8...10.0
Directional mode
1=Non-directional
2=Forward
3=Reverse
Time multiplier
0.05...15.00
Table continues on next page
226
Table 164:
67/50N-2 Input signals
Name
Type
I0 or IG or I2
SIGNAL
V0 or VG or V2
SIGNAL
BLOCK
BOOLEAN
ENA_MULT
BOOLEAN
RCA_CTL
BOOLEAN
Table 165:
67/51N Output signals
Name
Type
TRIP
BOOLEAN
PICKUP
BOOLEAN
Table 166:
67/50N Output signals
Name
Type
TRIP
BOOLEAN
PICKUP
BOOLEAN

Settings

Unit
Step
0.005
1)
xIn
0.1
0.01
Default
Description
0
Zero Sequence current / Negative sequence current
0
Zero Sequence voltage / Negative sequence voltage
0=False
Block signal for activating the blocking mode
0=False
Enable signal for current multiplier
0=False
Relay characteristic angle control
Description
Trip
Pickup
Description
Trip
Pickup
Default
Description
1
Pickup value
1.0
Multiplier for scaling the pickup value
2=Forward
Directional mode
1.00
Time multiplier in IEC/ANSI IDMT curves
1MAC504801-IB E
620 series ANSI
Technical Manual