R_Trig Function Block; F_Trig Function Block - ABB RELION 620 Series Technical Manual

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

Section 3
Basic functions
3.14.1.7
3.14.1.8
126
Function block
GUID-40218B77-8A30-445A-977E-46CB8783490D V1 EN
Figure 54:
Function block
Settings
The function does not have any parameters available in LHMI or Protection and Control
IED Manager (PCM600).

R_TRIG function block

Functionality
R_Trig is used as a rising edge detector.
R_Trig detects the transition from FALSE to TRUE at the CLK input. When the rising
edge is detected, the element assigns the output to TRUE. At the next execution round, the
output is returned to FALSE despite the state of the input.
Function block
GUID-3D0BBDC3-4091-4D8B-A35C-95F6289E6FD8 V1 EN
Figure 55:
Function block
Settings
The function does not have any parameters available in LHMI or Protection and Control
IED Manager (PCM600).

F_TRIG function block

Functionality
F_Trig is used as a falling edge detector.
The function detects the transition from TRUE to FALSE at the CLK input. When the
falling edge is detected, the element assigns the Q output to TRUE. At the next execution
round, the output is returned to FALSE despite the state of the input.
1MAC504801-IB E
620 series ANSI
Technical Manual

Advertisement