Three-phase underexcitation protection 40
Identification
This function is available in REM620 Ver.2.1 only.
Function description
Three-phase underexcitation protection
Function block
40
I3P
U3P
PICKUP
EXT_LOS_DET
BLOCK
BLK_TRIP
BLK_PICKUP
FR_TIMER
GUID-5DA20991-E63D-4243-8719-8CC3FD730266 V1 EN
Figure 244:
Function block
Functionality
The three-phase underexcitation protection 40 is used to protect the synchronous machine
against the underexcitation or loss of excitation condition.
The protection is based on the offset-mho circular characteristics on the impedance plane.
The function calculates the apparent impedance from the machine terminal voltages and
currents. If the impedance vector enters the offset-mho circle, the function gives the
operating signal after a set definite time. The operating time characteristics are according
to definite time (DT).
This function contains a blocking functionality. It is possible to block the function outputs,
timer or the function itself, if desired.
IEC 61850
identification
UEXPDIS
TRIP
Section 4
Protection functions
IEC 60617
ANSI/IEEE C37.2
identification
device number
X<
40