ABB RELION 620 Series Technical Manual page 89

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

1MAC504801-IB E
Table 39:
FR Non group settings
Parameter
Values (Range)
Operation
1=enable
5=disable
Trig mode
0=Trip or Pickup
1=Trip only
2=Pickup only
Measurement mode
1=RMS
2=DFT
3=Peak-to-Peak
620 series ANSI
Technical Manual
beginning of the fault if only a pickup event occurs during the fault. The maximum current
value collects the maximum fault currents during the fault. In case frequency cannot be
measured, nominal frequency is used for frequency and zero for Frequency gradient and
validity is set accordingly.
Measuring mode for phase current and residual current values can be selected with the
Measurement mode setting parameter.
Unit
Step
Table 40:
FR Monitored data
Name
Type
Fault number
INT32
Time and date
Timestamp
Pickup duration
FLOAT32
Trip time
FLOAT32
Breaker clear time
FLOAT32
Fault distance
FLOAT32
Fault resistance
FLOAT32
Fault loop Ris
FLOAT32
Fault loop React
FLOAT32
Setting group
INT32
Shot pointer
INT32
Table continues on next page
Default
Description
1=enable
Operation Disable / Enable
0=Trip or Pickup
Triggering mode
2=DFT
Selects used measurement mode
Values (Range)
Unit
0...999999
0.00...100.00
%
0.000...999999.99
s
9
0.000...999999.99
s
9
0.00...9999.99
pu
0.00...999.99
ohm
-1000.00...1000.
ohm
00
-1000.00...1000.0
ohm
0
1...6
0...7
Section 3
Basic functions
Description
Fault record
number
Fault record time
stamp
Maximum pickup
duration of all
stages during the
fault
Trip time
Breaker clear time
Distance to fault
measured in pu
Fault resistance
Resistance of fault
loop
Reactance of fault
loop,
PHDSTPDIS1
Active setting
group
Autoreclosing shot
pointer value
83