ABB RELION 620 Series Technical Manual page 546

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

Section 5
Protection-related functions
Parameter
Values (Range)
CB fault delay
0...60000
Measurement mode
2=DFT
3=Peak-to-Peak
Trip pulse time
0...60000
5.2.8
5.2.9
5.3
5.3.1
540
Unit
Step
ms
10
ms
10
Monitored data
Table 393:
50BF Monitored data
Name
Type
50BF
Enum
Technical data
Table 394:
50BF Technical data
Characteristic
Operation accuracy
Trip time accuracy
Master trip 86/94
Identification
Function description
Master trip
Default
Description
5000
Circuit breaker faulty delay
2=DFT
Phase current measurement mode of function
150
Pulse length of retrip and backup trip outputs
Values (Range)
Unit
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Value
Depending on the frequency of the measured
current: f
±2 Hz
n
±1.5% of the set value or ±0.002 × I
±1.0% of the set value or ±20 ms
IEC 61850
IEC 60617
identification
identification
TRPPTRC
Master Trip
1MAC504801-IB E
Description
Status
n
ANSI/IEEE C37.2
device number
86/94
620 series ANSI
Technical Manual

Advertisement

Table of Contents
loading

Table of Contents