ABB RELION 620 Series Technical Manual page 527

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

1MAC504801-IB E
4.7.3.8
Table 380:
40 Group settings
Parameter
Values (Range)
Diameter
1...6000
Offset
-1000...1000
Displacement
-1000...1000
Trip delay time
60...200000
Table 381:
40 Non group settings
Parameter
Values (Range)
Operation
1=enable
5=disable
Reset delay time
0...60000
External Los Det Ena
0=Disable
1=Enable
Voltage reversal
0=No
1=Yes
Impedance Meas mode
1=1Phase-to-earth
2=1Phase-to-
phase
3=3Phase-to-earth
4=3Phase-to-
phase
5=Pos sequence
Phase Sel for Z Clc
1=A or AB
2=B or BC
3=C or CA
620 series ANSI
Technical Manual
Name
Type
BLOCK
BOOLEAN
BLK_TRIP
BOOLEAN
BLK_PICKUP
BOOLEAN
FR_TIMER
BOOLEAN
Table 379:
40 Output signals
Name
Type
TRIP
BOOLEAN
PICKUP
BOOLEAN
Settings
Unit
Step
%Zn
1
%Zn
1
%Zn
1
ms
10
Unit
Step
ms
10
Default
Description
0=False
Block signal for activating the blocking mode
FALSE
Block signal for operate output
FALSE
Block signal for start
FALSE
Freeze signal for timer
Description
Trip
Pickup
Default
Description
200
Diameter of the Mho diagram
-10
Offset of top of the impedance circle from the
R-axis
0
Displacement of impedance circle centre from
the X-axis
5000
Trip delay time
Default
Description
5=disable
Operation Disable / Enable
3000
Reset delay time
1=Enable
Enable external excitation loss detection
0=No
Rotate voltage signals by 180 degrees
5=Pos sequence
Select voltage and currents for impedance
calculation
1=A or AB
Voltage phase selection
Section 4
Protection functions
521