The function can be enabled and disabled with the Operation setting. The corresponding
parameter values are "Enable" and "Disable". Additionally, each zone can be "On" or
"Off" individually with the help of the Operation Znx setting. When selected "On", the
particular zone is enabled, and respectively "Off" means a particular zone is disabled.
The operation of the phase step distance protection function can be described with a
module diagram. All the modules in the diagram are explained in the next sections.
GUID-9D582A33-E46E-4C1E-A848-E04C325AB17B V1 EN
Figure 230:
Functional module diagram
General Fault Criteria
The proper operation of 21P requires all three-phase currents and phase-to-phase or
phase-to-ground voltages to be available for measurement.
Reliable identification of fault and faulty phase(s) is done in a module called General Fault
Criteria or GFC. This function is compulsory to release the correct impedance-measuring
elements of the protection zones and to guarantee a selective operation of the phase
distance protection.
In GFC, the overcurrent method is used for identifying the faulty phase(s). The magnitude
of each phase current is compared to the Ph Str A Ph Sel GFC setting. If the phase current
magnitude exceeds the set limit, the respective phase is identified as faulty.