Section 12
General function block features
878
2
V
=
(
V
+ ⋅
a V
+
a V
1
A
B
C
GUID-7A6B6AAD-8DDC-4663-A72F-A3715BF3E56A-ANSI V1 EN
2
V
=
(
V
+
a V
+ ⋅
a V
2
A
B
C
GUID-6FAAFCC1-AF25-4A0A-8D9B-FC2FD0BCFB21-ANSI V1 EN
When VT connection is selected as "Delta", the positive and negative phase sequence
voltage components are calculated from the phase-to-phase voltages according to the
equations:
2
=
V
(
V
a V
) /
3
1
AB
BC
GUID-70796339-C68A-4D4B-8C10-A966BD7F090C-ANSI V1 EN
V
=
(
V
− ⋅
a V
) /
3
2
AB
BC
GUID-C132C6CA-B5F9-4DC1-94AF-FF22D2F0F12A-ANSI V1 EN
The phase-to-ground voltages are calculated from the phase-to-phase voltages when VT
connection is selected as "Delta" according to the equations.
(
)
V
=
V
+
V
V
3 /
A
0
AB
CA
GUID-1677DA47-81F3-4997-8D4D-5C955198C966 V1 EN
(
)
V
=
V
+
V
V
/ 3
B
0
BC
AB
GUID-BC8718B1-E189-4082-8F62-F46FF3215FDA V1 EN
(
)
V
=
V
+
V
V
/ 3
C
0
CA
BC
GUID-B4606B19-7510-461E-8A6B-9BFDF6F670DB V1 EN
If the
channel is not valid, it is assumed to be zero.
Vo
The phase-to-phase voltages are calculated from the phase-to-ground voltages when VT
connection is selected as "Wye" according to the equations.
V
=
V
V
AB
A
B
GUID-A2287CBF-D979-44CD-91ED-8CEBD120F1D8 V1 EN
=
V
V
V
BC
B
C
GUID-752436ED-0955-4C59-80C8-22DACEDE65D7 V1 EN
V
=
V
V
CA
C
A
GUID-4AE4B43A-B0A7-41DE-9C84-55527D9F6D78 V1 EN
) /
3
) /
3
1MAC504801-IB E
(Equation 123)
(Equation 124)
(Equation 125)
(Equation 126)
(Equation 127)
(Equation 128)
(Equation 129)
(Equation 130)
(Equation 131)
(Equation 132)
620 series ANSI
Technical Manual