620 series ANSI
Technical Manual
Requirements for measurement transformers
a few tens of watts because of the possible CT inaccuracy which might cause some current
through the stabilizing resistor in a normal load situation.
If V
is high or V
is low, a resistor with a higher power rating is needed. The resistor
kn
s
manufacturers often allow 10 times rated power for five seconds. The power of the resistor
can be calculated with
Equation
2
V
kn
R
10
s
GUID-168CAA1B-FEFE-41F3-8B60-6D9DBFF202DD V1 EN
The actual sensitivity of the protection is affected by the protection relay setting, the
magnetizing currents of the parallel connected CTs and the shunting effect of the voltage-
dependent resistor (VDR). The value of the primary current I
relay operates at a certain setting can be calculated with
(
I
n I
I
m I
= ⋅
+
+
prim
rs
u
m
GUID-A25EE549-D07B-4FEA-9DAF-DEFCADD6060F V1 EN
I
the primary current at which the protection is to start
prim
n
the turn ratio of the current transformer
I
the value of the
Operate value setting
rs
I
the leakage current flowing through the VDR at the V
u
m
the number of current transformers included in the protection per phase
I
the magnetizing current per current transformer at the V
m
The I
value given in many catalogs is the excitation current at the knee point voltage.
e
Assuming V
≈ 2 · V
, the value of
kn
s
The selection of current transformers can be divided into procedures.
1.
The rated current I
n
magnitude of I
.
kmax
2.
The rated primary current I
feeder.
58.
)
s
I
e
I
m
gives an approximate value for
2
of the feeder should be known. The value of I
of the CT must be higher than the rated current of the
1n
Section 13
at which the protection
prim
Equation
59.
voltage
voltage
s
also affects the
n
(Equation 136)
(Equation 137)
Equation
59.
885