Table 577:
TPS Non group settings
Parameter
Values (Range)
Cold load time
0...300
620 series ANSI
Technical Manual

Function block

TPS
IN1
OUT1
IN2
OUT2
GUID-D60C7A7E-032B-4CB9-87A3-ED39AE32D26A V2 EN
Figure 402:
Function block

Functionality

The minimum second pulse timer function TPS-1 contains two independent timers. The
function has a settable pulse length (in seconds). The timers are used for setting the
minimum pulse length for example, the signal outputs. Once the input is activated the
function gives out a pulse (Cold load time setting). But if the input remains active longer
than the set Cold load time, also the output remains active until the input is deactivated.
GUID-9BE17BA5-70D3-442B-8D24-8544C7A9441A V1 EN
Figure 403:
A = Trip pulse is shorter than Cold load time setting, B = Trip pulse is
longer than Cold load time setting

Signals

Table 576:
TPS Output signals
Name
Type
OUT1
BOOLEAN
OUT2
BOOLEAN

Settings

Unit
Step
s
1
Description
Output 1 status
Output 2 status
Default
Description
0
Cold load time
Section 11
Other functions
793