Section 4
Protection functions
4.5.2.8
4.5.2.9
4.5.3
4.5.3.1
388
Monitored data
Table 323:
49T Monitored data
Name
Type
TEMP
FLOAT32
TEMP_RL
FLOAT32
T_TRIP
INT32
T_ENA_CLOSE
INT32
49T
Enum
Technical data
Table 324:
49T Technical data
Characteristic
Operation accuracy
1)
Trip time accuracy
1) Overload current > 1.2 x Trip level temperature
Thermal overload protection for motors 49M
Identification
Function description
Thermal overload protection for motors
Values (Range)
Unit
-100.0...9999.9
°C
0.00...99.99
0...60000
s
0...60000
s
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Value
Depending on the frequency of the measured
current: f
±2 Hz
n
Current measurement: ±1.5% of the set value or
±0.002 x I
(at currents in the range of 0.01...4.00 x
n
I
)
n
±2.0% of the theoretical value or ±0.50 s
IEC 61850
IEC 60617
identification
identification
MPTTR
3Ith>M
1MAC504801-IB E
Description
The calculated temperature of
the protected object
The calculated temperature of
the protected object relative to
the trip level
Estimated time to trip
Estimated time to deactivate
BLK_CLOSE in seconds
Status
ANSI/IEEE C37.2
device number
49M
620 series ANSI
Technical Manual