User-programmable inverse-time characteristics
The user can define curves by entering parameters into the following standard formula:
A
[ ]
t s
B k
=
+
c
I
 −
E
I
>
A060641 V3 EN
t[s] Trip time (in seconds)
A
set
Curve parameter A
Curve parameter B
B
set
Curve parameter C
C
set
Curve parameter E
E
set
I
Measured current
Pickup value
I>
set
Time multiplier
k
set
RI and RD-type inverse-time characteristics
The RI-type simulates the behavior of electromechanical relays. The RD-type is a ground-
fault specific characteristic.
The RI-type is calculated using the formula
k
t s
[ ]
=
I
>
 
0 339 0 236
.
.
×
I
A060642 V2 EN
The RD-type is calculated using the formula
I
t s
[ ]
=
5 8 1 35 In
.
.
×
k I
× >
A060643 V2 EN
General function block features
 
Section 12
(Equation 107)
(Equation 108)
(Equation 109)
849