Settings; Monitored Data; Technical Data - ABB RELION 620 Series Technical Manual

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

Section 4
Protection functions
4.1.8.7
Table 182:
46PD Group settings
Parameter
Values (Range)
Pickup value
10...100
Trip delay time
100...30000
Table 183:
46PD Non group settings
Parameter
Values (Range)
Operation
1=enable
5=disable
Reset delay time
0...60000
Min phase current
0.05...0.30
4.1.8.8
4.1.8.9
244

Settings

Unit
Step
%
1
ms
1
Unit
Step
ms
1
xIn
0.01

Monitored data

Table 184:
46PD Monitored data
Name
Type
PICKUP_DUR
FLOAT32
RATIO_I2_I1
FLOAT32
46PD
Enum

Technical data

Table 185:
46PD Technical data
Characteristic
Operation accuracy
Pickup time
Reset time
Reset ratio
Retardation time
Trip time accuracy in definite time mode
Suppression of harmonics
Default
Description
10
Pickup value
1000
Trip delay time
Default
Description
5=disable
Operation Disable / Enable
20
Reset delay time
0.3
Minimum phase current
Values (Range)
Unit
0.00...100.00
%
0.00...999.99
%
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Value
Depending on the frequency of the measured
current: f
±2 Hz
n
±2% of the set value
<70 ms
<40 ms
Typically 0.96
<35 ms
±1.0% of the set value or ±20 ms
DFT: -50 dB at f = n × f
1MAC504801-IB E
Description
Ratio of pickup time / trip time
Measured current ratio I2 / I1
Status
, where n = 2, 3, 4, 5,...
n
620 series ANSI
Technical Manual