Parameter
Values (Range)
Input minimum
0...2000
Value unit
1=Dimensionless
5=Ampere
23=Degrees
celsius
30=Ohm
Value maximum
-10000.0...10000.0
Value minimum
-10000.0...10000.0
Val high high limit
-10000.0...10000.0
Value high limit
-10000.0...10000.0
Value low limit
-10000.0...10000.0
Value low low limit
-10000.0...10000.0
Value deadband
100...100000
Input mode
1=Not in use
2=Resistance
10=Pt100
11=Pt250
20=Ni100
21=Ni120
22=Ni250
30=Cu10
Input maximum
0...2000
Input minimum
0...2000
Value unit
1=Dimensionless
5=Ampere
23=Degrees
celsius
30=Ohm
Value maximum
-10000.0...10000.0
Value minimum
-10000.0...10000.0
Val high high limit
-10000.0...10000.0
Value high limit
-10000.0...10000.0
Value low limit
-10000.0...10000.0
Value low low limit
-10000.0...10000.0
Value deadband
100...100000
620 series ANSI
Technical Manual
Unit
Step
Default
1
0
1=Dimensionless
10000.0
-10000.0
10000.0
10000.0
-10000.0
-10000.0
1000
1=Not in use
1
2000
1
0
1=Dimensionless
10000.0
-10000.0
10000.0
10000.0
-10000.0
-10000.0
1000
Basic functions
Description
Minimum analogue input value for mA or
resistance scaling
Selected unit for output value format
Maximum output value for scaling and
supervision
Minimum output value for scaling and
supervision
Output value high alarm limit for supervision
Output value high warning limit for supervision
Output value low warning limit for supervision
Output value low alarm limit for supervision
Deadband configuration value for integral
calculation. (percentage of difference between
min and max as 0,001 % s)
Analogue input mode
Maximum analogue input value for mA or
resistance scaling
Minimum analogue input value for mA or
resistance scaling
Selected unit for output value format
Maximum output value for scaling and
supervision
Minimum output value for scaling and
supervision
Output value high alarm limit for supervision
Output value high warning limit for supervision
Output value low warning limit for supervision
Output value low alarm limit for supervision
Deadband configuration value for integral
calculation. (percentage of difference between
min and max as 0,001 % s)