Goosercv_Intl Function Block; Function Block; Functionality; Signals - ABB RELION 620 Series Technical Manual

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

Section 3
Basic functions
3.12.5
3.12.5.1
3.12.5.2
3.12.5.3
116
Table 60:
GOOSERCV_INT8 Output signals
Name
Type
OUT
INT8
VALID
BOOLEAN

GOOSERCV_INTL function block

Function block

GUID-241A36E0-1BB9-4323-989F-39668A7B1DAC V1 EN
Figure 44:
Function block

Functionality

The GOOSERCV_INTL function is used to connect the GOOSE double binary input to
the application and extracting single binary position signals from the double binary
position signal.
The OP output signal indicates that the position is open. Default value (0) is used if
VALID output indicates invalid status.
The CL output signal indicates that the position is closed. Default value (0) is used if
VALID output indicates invalid status.
The OK output signal indicates that the position is neither in faulty or intermediate state.
The default value (0) is used if VALID output indicates invalid status.

Signals

Table 61:
GOOSERCV_INTL Input signals
Name
Type
IN
Dbpos
Description
Output signal
Output signal
Default
Description
00
Input signal
1MAC504801-IB E
620 series ANSI
Technical Manual

Advertisement

Table of Contents
loading