620 series ANSI
Technical Manual
IL1
IL2
IL3
GUID-8DC3B17A-13FE-4E38-85C6-A228BC03206B-ANSI V2 EN
Figure 302:
Connection diagram for current circuit supervision with two sets of three-
phase current transformer protection cores
When using the measurement core for reference current measurement, it
should be noted that the saturation level of the measurement core is much
lower than with the protection core. This should be taken into account
when setting the current circuit supervision function.
Supervision functions
IED
CCM
I_A
FAIL
I_A
I_B
I_B
ALARM
I_C
I_C
I_REF
I_REF
BLOCK
Other protection devices
Section 6
593