Section 4
Protection functions
4.4.1.4
340
32P executes on the direction of positive-sequence power and not the
value. If overpower or underpower is needed, refer to 32O and 32U. 32P
is generally used for directional controls.

Operation principle

The function can be enabled and disabled with the Operation setting. The corresponding
parameter values are "Enable" and "Disable".
The operation of 32P can be described with a module diagram. All the modules in the
diagram are explained in the next sections.
V1
I1
BLOCK
GUID-D45D62FF-12ED-47FA-9B97-FF5BF0251AFE-ANSI V1 EN
Figure 152:
Functional module diagram
Directional detector
The Directional detector module compares the angle of the positive-sequence current I1
to the angle of the positive-sequence voltage V1. Using the positive-sequence voltage
angle as reference, the positive-sequence current angle is compared to the Characteristic
angle setting. If the angular difference is within the operating sector selected with the
Directional mode setting, the Enable signal is sent to Timer.
The operating sector is defined by the setting Min forward angle, Max forward angle, Min
reverse angle and Max reverse angle. The options that can be selected for the Directional
mode setting are "Forward" and "Reverse".
Timer
Directional
t
detector
Low level
blocking
Blocking
logic
1MAC504801-IB E
DIRECTION
RELEASE
620 series ANSI
Technical Manual