1MAC504801-IB E
6.7.6
Table 451:
CFD Group settings
Parameter
Values (Range)
PhPu
0...100000
CyMulit
1...20
AbsMinLoad
0...300
AdapPhPu
0=False
1=True
Table 452:
CFD Non group settings
Parameter
Values (Range)
Operation
1=enable
5=disable
6.7.7
620 series ANSI
Technical Manual
Settings
Unit
Step
10
1
10
Unit
Step
Monitored data
Table 453:
CFD Monitored data
Name
Type
SCDetect
BOOLEAN
Event3Ph
BOOLEAN
PickUpNoTripA
BOOLEAN
PickUpNoTripB
BOOLEAN
PickUpNoTripC
BOOLEAN
SCA
INT32
SCB
INT32
SCC
INT32
DetectfaultPhA
BOOLEAN
DetectfaultPhB
BOOLEAN
DetectfaultPhC
BOOLEAN
CFD
Enum
Default
Description
500
Fault Pickup parameter Threshold
5
Fault detect threshold parameter
100
Absolute min loading on the feeder
0=False
Adaptive phase pickup
Default
Description
5=disable
Operation Disable / Enable
Values (Range)
Unit
0=False
1=True
0=False
1=True
0=False
1=True
0=False
1=True
0=False
1=True
0...10000
0...10000
0...10000
0=False
1=True
0=False
1=True
0=False
1=True
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Section 6
Supervision functions
Description
SC Fault Detect
Three Phase Event
Pick up no trip Phase A
Pick up no trip Phase B
Pick up no trip Phase C
Number of faults in Phase A
Number of faults in Phase B
Number of faults in Phase C
Fault detected in Phase A
Fault detected in Phase B
Fault detected in Phase C
Status
625