8.1.7
Table 510:
PQI Non group settings
Parameter
Values (Range)
Operation
1=enable
5=disable
Demand interval
0=1 minute
1=5 minutes
2=10 minutes
3=15 minutes
4=30 minutes
5=60 minutes
6=180 minutes
Demand window
1=Sliding
2=Non-sliding
TDD alarm limit
1.0...100.0
Initial Dmd current
0.10...1.00
8.1.8
672
Settings
Unit
Step
%
0.1
xIn
0.01
Monitored data
Table 511:
PQI Monitored data
Name
Type
Max demand TDD IA
FLOAT32
Max demand TDD IB
FLOAT32
Max demand TDD IC
FLOAT32
Time max dmd TDD
Timestamp
IA
Time max dmd TDD
Timestamp
IB
Time max dmd TDD
Timestamp
IC
3SMHTDD_A
FLOAT32
DMD_TDD_A
FLOAT32
3SMHTDD_B
FLOAT32
DMD_TDD_B
FLOAT32
3SMHTDD_C
FLOAT32
DMD_TDD_C
FLOAT32
Default
Description
1=enable
Operation Disable / Enable
2=10 minutes
Time interval for demand calculation
1=Sliding
Demand calculation window type
50.0
TDD alarm limit
1.00
Initial demand current
Values (Range)
Unit
0.00...500.00
%
0.00...500.00
%
0.00...500.00
%
0.00...500.00
%
0.00...500.00
%
0.00...500.00
%
0.00...500.00
%
0.00...500.00
%
0.00...500.00
%
1MAC504801-IB E
Description
Maximum demand TDD for
phase A
Maximum demand TDD for
phase B
Maximum demand TDD for
phase C
Time of maximum demand
TDD phase A
Time of maximum demand
TDD phase B
Time of maximum demand
TDD phase C
3 second mean value of TDD
for phase A
Demand value for TDD for
phase A
3 second mean value of TDD
for phase B
Demand value for TDD for
phase B
3 second mean value of TDD
for phase C
Demand value for TDD for
phase C
620 series ANSI