When the Operation mode is set to "Toggle", the corresponding output toggles between
"True" and "False" for every input pulse received. The state of the output is stored in a
nonvolatile memory and restored if the protection relay is restarted.
When the Operation mode is set to "Pulsed", the corresponding output can be used to
produce the predefined length of pulses. Once activated, the output remains active for the
duration of the set pulse length. When activated, the additional activation command does
not extend the length of pulse. Thus, the pulse needs to be ended before the new activation
can occur.
The Description setting can be used for storing signal names for each output.
Each control point or LCNTRL can only be accessed through the LHMI control. LCNTRL
follows the local or remote (L/R) state if the Loc Rem restriction setting is "true". If the
Loc Rem restriction setting is "false", local or remote (L/R) state is ignored, that is, all
controls are allowed regardless of the local or remote state.
The BLOCK input can be used for blocking the output functionality. The BLOCK input
operation depends on the Operation mode setting. If the Operation mode setting is set to
"Toggle", the output state cannot be changed when the input BLOCK is TRUE. If the
Operation mode setting is set to "Pulsed", the activation of the BLOCK input resets the
output to the FALSE state.
From the remote communication point of view, SPCGGIO toggled
operation mode is always working as persistent mode. The output O#
follows the value written to the input IN#.
Signals
Table 594:
LCNTRL Input signals
Name
Type
BLOCK
BOOLEAN
Table 595:
LCNTRL Output signals
Name
Type
O1
BOOLEAN
O2
BOOLEAN
O3
BOOLEAN
O4
BOOLEAN
O5
BOOLEAN
Table continues on next page
Default
Description
0=False
Block signal for activating the blocking mode
Description
Output 1 status
Output 2 status
Output 3 status
Output 4 status
Output 5 status