1MAC504801-IB E
620 series ANSI
Technical Manual
blinder R and Outer blinder R intercepting at R-axis. The blinders are at the same angle as
the Impedance angle. The second blinder of each outer and inner pair is automatically
made symmetrical with the origin of the R-X plane.
For a correct operation, it is required that the setting for Inner blinder R is
less than the setting for Outer blinder R.
The circular mho characteristic can be further divided into two zones by setting Zone 2
enable to "Yes". The boundary between zones is set using the setting Zone 1 reach. The
lower portion of the circle, Zone 1, is separated from the upper portion, Zone 2, by a line,
perpendicular to the blinders, located at a set percentage of the Forward reach setting
from the origin.
-R
Outer
Inner
blinder
blinder
GUID-96D30A49-89E3-46B5-863E-69C483838C54 V1 EN
Figure 241:
Operating region for out of step with double blinder
A third zone, Zone 3, can be enabled by setting Zone 3 enable to "Yes". Zone 3 is defined
to include the area outside of the circular mho characteristic but inside a larger circle
centered on the origin that represents impedance with the magnitude of the minimum
positive-sequence current defined by setting Min Ps Seq current and the rated positive-
sequence voltage.
Figure 242
the zones should be coordinated with the settings for any distance protection functions.
X
Inner
Outer
-X
blinder
blinder
shows the three zones. Settings that determine the shape of
Protection functions
Impedance
angle
R
Section 4
505