ABB RELION 620 Series Technical Manual page 608

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

Section 6
Supervision functions
6.4.7
Table 435:
MCS 3I,I2 Non group settings
Parameter
Values (Range)
Operation
1=enable
5=disable
Min alarm current
0.01...0.50
Max alarm current
1.00...5.00
Max Ng Seq current
0.01...1.00
6.4.8
6.5
6.5.1
602
Table 434:
MCS 3I,I2 Output signals
Name
Type
FAIL
BOOLEAN
FAIL_CTGRP1
BOOLEAN
FAIL_CTGRP2
BOOLEAN
FAIL_CTGRP3
BOOLEAN
ALARM
BOOLEAN
Settings
Unit
Step
xIn
0.01
xIn
0.01
xIn
0.01
Monitored data
Table 436:
MCS 3I,I2 Monitored data
Name
Type
INT_BLKD
BOOLEAN
MCS 3I,I2
Enum
Fuse failure supervision 60
Identification
Function description
Fuse failure supervision
Description
CT secondary failure
CT secondary failure group 1
CT secondary failure group 2
CT secondary failure group 3
Alarm
Default
Description
1=enable
Operation Disable / Enable
0.02
Minimum alarm current
1.30
Maximum alarm current
0.10
Maximum I2 current in healthy set
Values (Range)
Unit
0=False
1=True
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
IEC 61850
IEC 60617
identification
identification
SEQRFUF
FUSEF
1MAC504801-IB E
Description
Function blocked internally
Status
ANSI/IEEE C37.2
device number
60
620 series ANSI
Technical Manual