Double-Pole Power Outputs Po3 And Po4 With Trip Circuit Supervision - ABB RELION 620 Series Technical Manual

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

1MAC504801-IB E
3.10.1.2
620 series ANSI
Technical Manual
PO1
PO2
GUID-4E1E21B1-BEEC-4351-A7BE-9D2DBA451985 V1 EN
Figure 22:
Dual single-pole power output contacts PO1 and PO2

Double-pole power outputs PO3 and PO4 with trip circuit supervision

The power outputs PO3 and PO4 are double-pole normally open/form A power outputs
with trip circuit supervision.
When the two poles of the contacts are connected in series, they have the same technical
specification as PO1 for breaking duty. The trip circuit supervision hardware and
associated functionality which can supervise the breaker coil both during closing and
opening condition are also provided. Contacts PO3 and PO4 are almost always used for
energizing the breaker trip coils.
X100
6
7
8
9
Section 3
Basic functions
91

Advertisement

Table of Contents
loading

Table of Contents