Signals; Settings - ABB RELION 620 Series Technical Manual

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

1MAC504801-IB E
4.2.3.6
4.2.3.7
Table 233:
59G/N Group settings
Parameter
Values (Range)
Pickup value
0.010...1.000
Trip delay time
40...300000
Table 234:
59G/N Non group settings
Parameter
Values (Range)
Operation
1=enable
5=disable
Reset delay time
0...60000
VG/V0 Select
1=Measured VG
2=Calculated V0
620 series ANSI
Technical Manual
Therefore, this function is often used as a back-up protection or as a release signal for the
feeder ground-fault protection.
The protection can also be used for the ground-fault protection of generators and motors
and for the unbalance protection of capacitor banks.
The ground voltage can be calculated internally based on the measurement of the three-
phase voltage. This voltage can also be measured by a single-phase voltage transformer,
located between a transformer star point and ground, or by using an open-delta connection
of three single-phase voltage transformers.

Signals

Table 231:
59G/N Input signals
Name
Type
VG
SIGNAL
BLOCK
BOOLEAN
Table 232:
59G/N Output signals
Name
Type
TRIP
BOOLEAN
PICKUP
BOOLEAN

Settings

Unit
Step
xVn
0.001
ms
1
Unit
Step
ms
1
Default
Description
0
Ground voltage
0=False
Block signal for activating the blocking mode
Description
Trip
Pickup
Default
Description
0.1
Pickup value
40
Trip delay time
Default
Description
5=disable
Operation Disable / Enable
20
Reset delay time
1=Measured VG
Selection for used VG/V0 signal
Section 4
Protection functions
285