Signals; Settings - ABB RELION 620 Series Technical Manual

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

Section 9
Control functions
9.1.6
9.1.7
Table 533:
52 Non group settings
Parameter
Values (Range)
Operation
1=enable
5=disable
Select timeout
10000...300000
Pulse length
10...60000
Operation counter
0...10000
Table continues on next page
710

Signals

Table 531:
52 Input signals
Name
Type
ENA_OPEN
BOOLEAN
ENA_CLOSE
BOOLEAN
BLK_OPEN
BOOLEAN
BLK_CLOSE
BOOLEAN
ITL_BYPASS
BOOLEAN
AU_OPEN
BOOLEAN
AU_CLOSE
BOOLEAN
POSOPEN
BOOLEAN
POSCLOSE
BOOLEAN
1) Not available for monitoring
Table 532:
52 Output signals
Name
Type
SELECTED
BOOLEAN
EXE_OP
BOOLEAN
EXE_CL
BOOLEAN
OPENPOS
BOOLEAN
CLOSEPOS
BOOLEAN
OKPOS
BOOLEAN
OPEN_ENAD
BOOLEAN
CLOSE_ENAD
BOOLEAN

Settings

Unit
Step
ms
10000
ms
1
Default
Description
1=True
Enables opening
1=True
Enables closing
0=False
Blocks opening
0=False
Blocks closing
0=False
Discards ENA_OPEN and ENA_CLOSE interlocking
when TRUE
0=False
Input signal used to open the breaker
0=False
Input signal used to close the breaker
0=False
Signal for open position of apparatus from I/O
0=False
Signal for closed position of apparatus from I/O
Description
Object selected
Executes the command for open direction
Executes the command for close direction
Apparatus open position
Apparatus closed position
Apparatus position is ok
Opening is enabled based on the input status
Closing is enabled based on the input status
Default
Description
1=enable
Operation mode disable / disable
60000
Select timeout in ms
100
Open and close pulse length
0
Breaker operation cycles
1MAC504801-IB E
1)
1)
1)
1)
620 series ANSI
Technical Manual