Section 4
Protection functions
Parameter
Values (Range)
Measurement mode
1=RMS
2=DFT
3=Peak-to-Peak
Min trip current
0.005...1.000
Min trip voltage
0.01...1.00
Correction angle
0.0...10.0
Pol reversal
0=False
1=True
Curve parameter A
0.0086...120.0000
Curve parameter B
0.0000...0.7120
Curve parameter C
0.02...2.00
Curve parameter D
0.46...30.00
Curve parameter E
0.0...1.0
IG/I0 signal Sel
1=Measured IG
2=Calculated I0
Pol signal Sel
1=Measured VG
2=Calculated V0
3=Neg. seq. volt.
1) The value of In is determined by the
Current (Io, CT)/Secondary current. If
Secondary current, since I0 is calculated by summing the phase currents.
Table 169:
67/50N Group settings
Parameter
Values (Range)
Pickup value
0.10...40.00
Pickup value mult
0.8...10.0
Directional mode
1=Non-directional
2=Forward
3=Reverse
Time multiplier
0.05...15.00
Operating curve type
1=ANSI Ext Inv
3=ANSI Norm Inv
5=ANSI DT
15=IEC DT
17=Programmable
Type of reset curve
1=Immediate
2=Def time reset
3=Inverse reset
Trip delay time
40...200000
Table continues on next page
228
Unit
Step
0.001
1)
xIn
xVn
0.01
deg
0.1
I0 signal Sel setting. If I0 signal Sel = Measured IG, then In is the value set in Configuration/Analog inputs/
I0 signal Sel = Calculated I0, then In is the value set in Configuration/Analog inputs/Current (3I, CT)/
Unit
Step
0.01
1)
xIn
0.1
0.01
ms
10
Default
Description
2=DFT
Selects used measurement mode
0.005
Minimum trip current
0.01
Minimum trip voltage
0.0
Angle correction
0=False
Rotate polarizing quantity
28.2000
Parameter A for customer programmable
curve
0.1217
Parameter B for customer programmable
curve
2.00
Parameter C for customer programmable
curve
29.10
Parameter D for customer programmable
curve
1.0
Parameter E for customer programmable
curve
2=Calculated I0
Selection for used Io signal
2=Calculated V0
Selection for used polarization signal
Default
Description
0.5
Pickup value
1.0
Multiplier for scaling the pickup value
2=Forward
Directional mode
1.00
Time multiplier in IEC/ANSI IDMT curves
5=ANSI DT
Selection of time delay curve type
1=Immediate
Selection of reset curve type
60
Trip delay time
1MAC504801-IB E