Table 658:
Insulation tests
Description
Dielectric tests
Impulse voltage test
Insulation resistance
measurement
Protective bonding resistance
Table 659:
Environmental tests
Description
Damp heat test
Dry heat test
Dry cold test
Storage temperature test
Change temperature test
1) The auxiliary voltage was disconnected during the first 5 cycles of the test. The auxiliary voltage was
switched on during the sixth cycle when the temperature was +55°C and the humidity 95% Rh.
2) Protection relay was soaked unpowered for 12 hours and then checked for functionality.
3) LCD may be unreadable, but the protection relay is still operational.
4) For protection relays with an LC communication interface, the maximum operating temperature is +70°C.
5) Protection relay was energized.
Protection relay and functionality tests
Requirement
2.8 kV DC, 1 min
700 V, DC, 1 min for signal circuit and
communication
2 kV AC 50 Hz, 1 min
500 V AC 50 Hz, 1 min for
communication
5 kV, 1.2/50 μs, 0.5 J
>100 MΩ, 500 V
DC
<0.1 Ω, 4 A, 60 s
Requirement
+55°C, Rh = 95%, 96 h
6 test cycles (12 h + 12 h), +25...
1)
+55°C, Rh = 95%
2)3)4)
+85°C 12h
3)4)
+85°C 16 h
+55°C 96h
2)3)
-40°C 12 h
3)
-40°C 16 h
-25°C 96 h
+85°C 96 h, -40°C 96 h
5 test cycles (3 h + 3 h) at -25°C
5)
and +55°C
Section 16
Reference
IEEE C37.90-2005
IEC 60255-5
IEEE C37.90-2005
IEC 60255-5
IEC 60255-27
Reference
IEEE C37.90-2005
IEC 60068-2-30
IEEE C37.90-2005
IEC 60068-2-2
IEEE C37.90-2005
IEC 60068-2-1
IEEE C37.90-2005
IEC 60068-2-1,-2
IEC 60068-2-14
917