Section 9
Control functions
708
interlocking signals can be transferred with a bus. All secured control operations require
two-step commands: a selection step and an execution step. The secured object control is
responsible for the several tasks.
Command authority: ensures that the command source is authorized to operate the
object
Mutual exclusion: ensures that only one command source at a time can control the
object
Interlocking: allows only safe commands
Execution: supervises the command execution
Command canceling: cancels the controlling of a selected object.
In direct operation, a single message is used to initiate the control action of a physical
device. The direct operation method uses less communication network capacity and
bandwidth than the SBO method, because the procedure needs fewer messages for
accurate operation.
52
Selected
52
to operate
GUID-80B170A6-C091-4F8E-BF99-919B8A180917-ANSI V1 EN
Figure 356:
Control procedure in SBO method
1. Send reservation to other terminals
2. Receive response
52
52
1MAC504801-IB E
52
620 series ANSI
Technical Manual