Section 4
Protection functions
4.4.1.5
4.4.1.6
4.4.1.7
Table 282:
32P Group settings
Parameter
Values (Range)
Release delay time
0...1000
Characteristic angle
-179...180
Max forward angle
0...90
Max reverse angle
0...90
Min forward angle
0...90
Min reverse angle
0...90
Directional mode
1=Non-directional
2=Forward
3=Reverse
342
Blocking logic
The binary input BLOCK can be used to block the function. The activation of the BLOCK
input deactivates the RELEASE output and resets Timer.

Application

The three-phase directional power protection 32P improves the possibility to obtain a
selective function of the overcurrent protection in meshed networks. 32P is used to block
or release other overcurrent protection functions.

Signals

Table 280:
32P Input signals
Name
Type
V1
REAL
I1
REAL
BLOCK
BOOLEAN
Table 281:
32P Output signals
Name
Type
RELEASE
BOOLEAN
DIRECTION
Enum

Settings

Unit
Step
ms
1
deg
1
deg
1
deg
1
deg
1
deg
1
Default
Description
0.0
Positive sequence voltage
0.0
Positive sequence current
0=False
Block signal for activating the blocking mode
Description
direction signal
Direction information
Default
Description
10
Release delay time
60
Characteristic angle
88
Maximum phase angle in forward direction
88
Maximum phase angle in reverse direction
88
Minimum phase angle in forward direction
88
Minimum phase angle in reverse direction
2=Forward
Directional mode
1MAC504801-IB E
620 series ANSI
Technical Manual