Section 6
Supervision functions
6.8.5
6.8.6
628
Application
The machine operating time since commissioning indicates the use of the machine. For
example, the mechanical wear and lubrication requirement for the shaft bearing of the
motors depend on the use hours.
If some motor is used for long duration runs, it might require frequent servicing, while for
a motor that is not used regularly the maintenance and service are scheduled less
frequently. The accumulated operating time of a motor together with the appropriate
settings for warning can be utilized to trigger the condition based maintenance of the
motor.
The operating time counter combined with the subsequent reset of the operating-time
count can be used to monitor the motor's run time for a single run.
Both the long term accumulated operating time and the short term single run duration
provide valuable information about the condition of the machine and device. The
information can be co-related to other process data to provide diagnoses for the process
where the machine or device is applied.
Signals
Table 454:
OPTM Input signals
Name
Type
BLOCK
BOOLEAN
POS_ACTIVE
BOOLEAN
RESET
BOOLEAN
Table 455:
OPTM Output signals
Name
Type
ALARM
BOOLEAN
WARNING
BOOLEAN
Default
Description
0=False
Block input status
0=False
When active indicates the equipment is running
0=False
Resets the accumulated operation time to initial value
Description
Alarm accumulated operation time exceeds Alarm value
Warning accumulated operation time exceeds Warning
value