4.3.2.6
620 series ANSI
Technical Manual
Table 272:
Setting for a five-step df/dt< operation
Load-shedding steps
1
2
3
4
5
Once the frequency has stabilized, the shed load can be restored. The restoring operation
should be done stepwise, taking care that it does not lead the system back to the emergency
condition.
Table 273:
Setting for a five-step restoring operation
Load-shedding steps
1
2
3
4
5

Signals

Table 274:
81LSH Input signals
Name
Type
F
SIGNAL
dF/dt
SIGNAL
BLOCK
BOOLEAN
BLK_REST
BOOLEAN
MAN_RESTORE
BOOLEAN
Table 275:
81LSH Output signals
Name
Type
TRIP
BOOLEAN
OPR_FRQ
BOOLEAN
OPR_FRG
BOOLEAN
PICKUP
BOOLEAN
ST_FRQ
BOOLEAN
Table continues on next page
Pickup value df/dt setting
-0.005 · Fn /s (-0.25 Hz/s)
-0.010 · Fn /s (-0.25 Hz/s)
-0.015 · Fn /s (-0.25 Hz/s)
-0.020 · Fn /s (-0.25 Hz/s)
-0.025 · Fn /s (-0.25 Hz/s)
Restoring pickup Val setting
0.990 · Fn (59.4 Hz)
0.990 · Fn (59.4 Hz)
0.990 · Fn (59.4 Hz)
0.990 · Fn (59.4 Hz)
0.990 · Fn (59.4 Hz)
Default
Description
0
Measured frequency
0
Rate of change of frequency
0=False
Block signal for activating the blocking mode
0=False
Block restore
0=False
Manual restore signal
Description
Trip of load shedding
Trip signal for under frequency
Trip signal for high df/dt
Pickup
Pick-Up signal for under frequency detection
Section 4
Protection functions
Trip Tm df/dt setting
8000 ms
2000 ms
1000 ms
500 ms
250 ms
Restore delay time setting
200000 ms
160000 ms
100000 ms
50000 ms
10000 ms
337