Settings - ABB RELION 620 Series Technical Manual

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

1MAC504801-IB E
4.2.2.8
Table 227:
27 Group settings
Parameter
Values (Range)
Pickup value
0.05...1.20
Time multiplier
0.05...15.00
Trip delay time
60...300000
Operating curve type
5=ANSI DT
15=IEC DT
21=Inv. Curve A
22=Inv. Curve B
23=Programmable
Type of reset curve
1=Immediate
2=Def time reset
-1=DT Lin decr rst
Table 228:
27 Non group settings
Parameter
Values (Range)
Operation
1=enable
5=disable
Num of pickup phases
1=1 out of 3
2=2 out of 3
3=3 out of 3
Minimum trip time
60...60000
Reset delay time
0...60000
Curve parameter A
0.005...200.000
Curve parameter B
0.50...100.00
Curve parameter C
0.0...1.0
Curve parameter D
0.000...60.000
Curve parameter E
0.000...3.000
Curve Sat Relative
0.0...3.0
Voltage block value
0.05...1.00
Enable block value
0=False
1=True
Voltage selection
1=phase-to-earth
2=phase-to-phase
Relative hysteresis
1.0...5.0
620 series ANSI
Technical Manual

Settings

Unit
Step
xVn
0.01
0.01
ms
10
Unit
Step
ms
1
ms
1
0.1
xVn
0.01
%
0.1
Default
Description
0.90
Pickup value
1.00
Time multiplier in IEC/ANSI IDMT curves
60
Trip delay time
5=ANSI DT
Selection of time delay curve type
1=Immediate
Selection of reset curve type
Default
Description
5=disable
Operation Disable / Enable
1=1 out of 3
Number of phases required for trip activation
60
Minimum trip time for IDMT curves
20
Reset delay time
1.000
Parameter A for customer programmable
curve
1.00
Parameter B for customer programmable
curve
0.0
Parameter C for customer programmable
curve
0.000
Parameter D for customer programmable
curve
1.000
Parameter E for customer programmable
curve
2.0
Tuning parameter to avoid curve
discontinuities
0.20
Low level blocking for undervoltage mode
1=True
Enable internal blocking
2=phase-to-phase
Parameter to select phase or phase-to-phase
voltages
4.0
Relative hysteresis for operation
Section 4
Protection functions
281