Section 3
Basic functions
Table 24:
COM2 serial communication settings
Parameter
Values (Range)
Fiber mode
0=No fiber
2=Fiber light OFF
loop
Serial mode
1=RS485 2Wire
2=RS485 4Wire
3=RS232 no
handshake
4=RS232 with
handshake
CTS delay
0...60000
RTS delay
0...60000
Baudrate
1=300
2=600
3=1200
4=2400
5=4800
6=9600
7=19200
8=38400
9=57600
10=115200
Table 25:
Time settings
Parameter
Values (Range)
Date
Time
Time format
1=24H:MM:SS:MS
2=12H:MM:SS:MS
Date format
1=DD.MM.YYYY
2=DD/MM/YYYY
3=DD-MM-YYYY
4=MM.DD.YYYY
5=MM/DD/YYYY
6=YYYY-MM-DD
7=YYYY-DD-MM
8=YYYY/DD/MM
Table continues on next page
62
If this protocol does not operate as expected, check that another serial
protocol is not using the same COM port.
DNP3 protocol ignores any parity setting in the COM settings group;
DNP3 is defined as an 8 bit/no parity protocol with a 16-bit CRC every 16
bytes. This provides better error detection than parity.
Unit
Step
Default
0=No fiber
1=RS485 2Wire
0
0
6=9600
Unit
Step
Default
0
0
1=24H:MM:SS:M
S
5=MM/DD/YYYY
1MAC504801-IB E
Description
Fiber mode for COM2
Serial mode for COM2
CTS delay for COM2
RTS delay for COM2
Baudrate for COM2
Description
Date
Time
Time format
Date format
Technical Manual
620 series ANSI