ABB RELION 620 Series Technical Manual page 262

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

Section 4
Protection functions
256
I_A
I_B
detector 1
I_C
detector 2
BLOCK
GUID-4A6308B8-47E8-498D-A268-1386EBBBEC8F-ANSI V1 EN
Figure 117:
Functional module diagram
Level detector 1
This module compares the phase currents (RMS value) to the set Pickup value high
setting. If all the phase current values are less than the set Pickup value high value, the loss
of load condition is detected and an enable signal is sent to the timer. This signal is
disabled after one or several phase currents have exceeded the set Pickup value high value
of the element.
Level detector 2
This is a low-current detection module, which monitors the de-energized condition of the
motor. It compares the phase currents (RMS value) to the set Pickup value low setting. If
any of the phase current values is less than the set Pickup value low, a signal is sent to block
the operation of the timer.
Timer
Once activated, the timer activates the PICKUP output. The time characteristic is
according to DT. When the trip timer has reached the value set by Trip delay time, the
TRIP output is activated. If the fault disappears before the module trips, the reset timer is
activated. If the reset timer reaches the value set by Reset delay time, the trip timer resets
and the PICKUP output is deactivated.
The timer calculates the pickup duration value PICKUP_DUR, which indicates the
percentage ratio of the pickup situation and the set trip time. The value is available in the
monitored data view.
The BLOCK signal blocks the operation of the function and resets the timer.
Timer
Level
t
Level
1MAC504801-IB E
PICKUP
TRIP
620 series ANSI
Technical Manual