1MAC504801-IB E
Section 11
11.1
11.1.1
11.1.1.1
11.1.1.2
11.1.1.3
620 series ANSI
Technical Manual
Other functions
Minimum pulse timer
Minimum pulse timer TP
Identification
Functional description
Minimum pulse timer (2 pcs)
Function block
GUID-976C7618-9B29-4C4C-B154-FC3F2B8CC470 V1 EN
Figure 400:
Function block
Functionality
The Minimum pulse timer function TP contains two independent timers running in
milliseconds. The function has a settable pulse length (in milliseconds). The timers are
used for setting the minimum pulse length for example, the signal outputs. Once the input
is activated the function gives out a pulse (Pulse time setting). But if the input remains
active longer than the set Pulse time, also the output remains active until the input is
deactivated.
IEC 61850
IEC 60617
identification
identification
TPGAPC
TP
Section 11
Other functions
ANSI/IEEE C37.2
device number
TP
791