Settings; Monitored Data - ABB RELION 620 Series Technical Manual

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

1MAC504801-IB E
4.4.3.7
Table 295:
32O Group settings
Parameter
Values (Range)
Pickup value
0.01...2.00
Trip delay time
40...300000
Directional mode
1=Non-directional
2=Forward
3=Reverse
Power angle
-90...90
Table 296:
32O Non group settings
Parameter
Values (Range)
Operation
1=enable
5=disable
Measurement mode
1=PhsA, PhsB,
PhsC
2=Arone
3=Pos Seq
4=PhsAB
5=PhsBC
6=PhsCA
7=PhsA
8=PhsB
9=PhsC
Reset delay time
0...60000
Pol reversal
0=False
1=True
4.4.3.8
620 series ANSI
Technical Manual

Settings

Unit
Step
%Sn
0.01
ms
10
deg
1
Unit
Step
ms
10

Monitored data

Table 297:
32O Monitored data
Name
Type
PICKUP_DUR
FLOAT32
P
FLOAT32
Q
FLOAT32
S
FLOAT32
PF_ANGLE
FLOAT32
32O
Enum
Default
Description
1.00
Pickup value
40
Trip delay time
2=Forward
Directional mode
0
Adjustable angle for power
Default
Description
5=disable
Operation Enable / Disable
3=Pos Seq
Selection of power calculation method
20
Reset delay time
0=False
Reverse the definition of the power direction
Values (Range)
Unit
0.00...100.00
%
-160.000...160.0
xSn
00
-160.000...160.0
xSn
00
-160.000...160.0
xSn
00
-180.00...180.00
deg
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Section 4
Protection functions
Description
Ratio of pickup time / trip time
Active power
Reactive power
Apparent power
Power factor angle
Status
359