1MAC504801-IB E
Parameter
Values (Range)
Min reverse angle
0...90
Voltage Mem time
0...3000
Pol quantity
-2=Pos. seq. volt.
1=Self pol
4=Neg. seq. volt.
5=Cross pol
Table 130:
67/50P Non group settings
Parameter
Values (Range)
Operation
1=enable
5=disable
Reset delay time
0...60000
Minimum trip time
20...60000
Allow Non Dir
0=False
1=True
Measurement mode
1=RMS
2=DFT
3=Peak-to-Peak
Min trip current
0.01...1.00
Min trip voltage
0.01...1.00
Curve parameter A
0.0086...120.0000
Curve parameter B
0.0000...0.7120
Curve parameter C
0.02...2.00
Curve parameter D
0.46...30.00
Curve parameter E
0.0...1.0
Num of pickup phases
1=1 out of 3
2=2 out of 3
3=3 out of 3
620 series ANSI
Technical Manual
Unit
Step
Default
deg
1
80
ms
1
40
5=Cross pol
Unit
Step
Default
5=disable
ms
1
20
ms
1
20
0=False
2=DFT
xIn
0.01
0.01
xVn
0.01
0.01
28.2000
0.1217
2.00
29.10
1.0
1=1 out of 3
Protection functions
Description
Minimum phase angle in reverse direction
Voltage memory time
Reference quantity used to determine fault
direction
Description
Operation Disable / Enable
Reset delay time
Minimum trip time for IDMT curves
Allows prot activation as non-dir when dir info is
invalid
Selects used measurement mode
Minimum trip current
Minimum trip voltage
Parameter A for customer programmable
curve
Parameter B for customer programmable
curve
Parameter C for customer programmable
curve
Parameter D for customer programmable
curve
Parameter E for customer programmable
curve
Number of phases required for trip activation
Section 4
185