Section 15
Technical data
910
Table 644:
Signal outputs and IRF output
Description
Rated voltage
Continuous contact carry
Make and carry for 3.0 s
Make and carry 0.5 s
Breaking capacity when the control-circuit time
constant L/R <40 ms, at 48/110/220 V DC
Minimum contact load
1) X100: IRF, SO2
X105: SO3, SO4, when REF620 or RET620 is equipped with BIO0005
X110: SO3, SO4, when any of the protection relays is equipped with BIO0005
X115: SO3, SO4 when REF620 is equipped with BIO0005
X130: SO3, when REM620 is equipped with BIO0006
X130: SO1, SO2, when RET620 is equipped with RTD0002
Table 645:
Double-pole power outputs with TCM function X100: PO3 and PO4
Description
Rated voltage
Continuous contact carry
Make and carry for 3.0 s
Make and carry for 0.5 s
Breaking capacity when the control-circuit time
constant L/R <40 ms, at 48/110/220 V DC (two
contacts connected in a series)
Minimum contact load
Trip-circuit monitoring (TCM)
Control voltage range
Current drain through the monitoring circuit
Minimum voltage over the TCS contact
1) PSM0003: PO3, PSM0004: PO3, PSM0003: PO4 and PSM0004: PO4.
Table 646:
Signal/trip output with high make and carry and with TCM function
Description
Rated voltage
Continuous contact carry
Make and carry for 3.0 s
Table continues on next page
1)
Value
250 V AC/DC
5 A
10 A
15 A
1 A/0.25 A/0.15 A
10 mA at 5 V AC/DC
1)
Value
250 V AC/DC
8 A
15 A
30 A
5 A/3 A/1 A
100 mA at 24 V AC/DC
20...250 V AC/DC
~1.5 mA
20 V AC/DC (15...20 V)
1)
Value
250 V AC/DC
5 A
15 A
1MAC504801-IB E
620 series ANSI
Technical Manual