Directional Overpower Protection Goppdop; Identification; Application - ABB RES670 Applications Manual

Relion 670 series phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

1MRK 511 407-UEN C
8.7
8.7.1
8.7.2
Phasor measurement unit RES670 2.2 IEC
Application manual
(
)
= ×
+
-
×
S
k S
1
k S
Old
Calculated
EQUATION1893 V1 EN-US
Where
S
is a new measured value to be used for the protection function
S
is the measured value given from the function in previous execution cycle
old
S
is the new calculated value in the present execution cycle
Calculated
k
is settable parameter
The value of k=0.92 is recommended in generator applications as the trip delay is
normally quite long.
The calibration factors for current and voltage measurement errors are set % of
rated current/voltage:
IAmpComp5, IAmpComp30, IAmpComp100
UAmpComp5, UAmpComp30, UAmpComp100
IAngComp5, IAngComp30, IAngComp100
The angle compensation is given as difference between current and voltage angle
errors.
The values are given for operating points 5, 30 and 100% of rated current/voltage.
The values should be available from instrument transformer test protocols.

Directional overpower protection GOPPDOP

Identification

Function description
Directional overpower protection

Application

The task of a generator in a power plant is to convert mechanical energy available
as a torque on a rotating shaft to electric energy.
Current protection
IEC 61850
IEC 60617
identification
identification
GOPPDOP
P >
2
DOCUMENT172362-IMG158942
V2 EN-US
Section 8
(Equation 67)
SEMOD172360-1 v4
SEMOD176574-2 v4
ANSI/IEEE C37.2
device number
32
SEMOD172358-4 v2
165