Motor load jam protection 51LR

Identification

Function description
Motor load jam protection

Function block

GUID-E6B45EAE-D0FA-4310-AA47-6F03A7B5EBBE V2 EN
Figure 118:
Function block

Functionality

The Motor load jam protection 51LR is used for protecting the motor in stall or mechanical
jam situations during the running state.
When the motor is started, a separate function is used for the startup protection, and 51LR
is normally blocked during the startup period. When the motor has passed the starting
phase, 51LR monitors the magnitude of phase currents. The function starts when the
measured current exceeds the breakdown torque level, that is, above the set limit. The
operation characteristic is definite time.
The function contains a blocking functionality. It is possible to block the function outputs.
The 51LR does not provide a valid trip time in the fault records by default.
If this functionality is desired, the PICKUP status must be added to the
61850 data set which also causes all 51LR pickup events to be reported.
See the 61850 engineering manual for more information on how to add
items to the 61850 data set.

Operation principle

The function can be enabled and disabled with the Operation setting. The corresponding
parameter values are "Enable" and "Disable".
IEC 61850
IEC 60617
identification
identification
JAMPTOC
Ist>
Section 4
Protection functions
ANSI/IEEE C37.2
device number
51LR
259