Technical Manual
Local generic control points LCNTRL
Identification
Function description
Local generic control points
Function block
GUID-40CEB788-AF42-4DA3-AC5A-A168A6F6585E V1 EN
Figure 412:
Function block
Functionality
The local control function block LCNTRL is dedicated only for local controlling, that is,
LCNTRL cannot be controlled remotely. The local control is done through the buttons in
the front panel.
Operation principle
The function can be enabled and disabled with the Operation setting. The corresponding
parameter values are "Enable" and "Disable".
LCNTRL has the Operation mode, Pulse length and Description settings available to
control all 16 outputs. By default, the Operation mode setting is set to "Off". This disables
the controllable signal output. LCNTRL also has a general setting Loc Rem restriction,
which enables or disables the local or remote state functionality.
IEC 61850
IEC 60617
identification
identification
SPCLGGIO
SPCL
Section 11
Other functions
ANSI/
IEEEidentification
LCNTRL