Minimum minute pulse timer TPM

Identification

Functional description
Minimum minute pulse timer (2 pcs)

Function block

TPM
IN1
OUT1
IN2
OUT2
GUID-3F486DF9-0D33-4D5F-9A57-BF1E9FD7C3DA V2 EN
Figure 404:
Function block

Functionality

The minimum minute pulse timer function TPM contains two independent timers. The
function has a settable pulse length (in minutes). The timers are used for setting the
minimum pulse length for example, the signal outputs. Once the input is activated the
function gives out a pulse (Cold load time setting). But if the input remains active longer
than the set Cold load time, also the output remains active until the input is deactivated.
GUID-9BE17BA5-70D3-442B-8D24-8544C7A9441A V1 EN
Figure 405:
A = Trip pulse is shorter than Cold load time setting, B = Trip pulse is
longer than Cold load time setting
IEC 61850
IEC 60617
identification
identification
TPMGAPC
TPM
1MAC504801-IB E
ANSI/IEEE C37.2
device number
62-CLD
TPM
620 series ANSI
Technical Manual